VG DS Series Air-Cooled Chiller (50–200 kW)
Twin scroll; two compressors in the existing table. VG DS 55 has a plate evaporator; the other listed models have shell-and-tube evaporators.

Twin scroll; two compressors in the existing table. VG DS 55 has a plate evaporator; the other listed models have shell-and-tube evaporators.
How to read the capacity range
The series label is a commercial range. Evaluate model-table values together with their rating conditions. For final selection, specify leaving-water temperature, ambient conditions and glycol concentration, then request model performance data at that duty.
Project inputs and calculation boundaries
For a quotation, specify approximate heat duty, fluid, inlet and outlet temperatures, flow, pressure loss and operating hours. Design ambient conditions, indoor or outdoor location and electrical infrastructure are also selection inputs. Flow and temperature readings must represent the same operating point. Do not transfer a catalogue capacity directly to different temperatures; confirm model performance at the required duty.
Commissioning and operating records
Check circuit cleanliness, filtration, air removal, proven flow and sensor readings. Record reference water temperatures and load conditions during commissioning. These values provide a baseline for maintenance and alarm investigations. Confirm pumps, tanks, connections and control options against the agreed quotation scope.
Frequently asked questions
Is the series capacity range sufficient for final selection?
No. Confirm the actual model at the required fluid temperature, ambient conditions, fluid properties and hydraulic duty.
Is cooling capacity the electrical consumption?
No. Cooling kW and electrical-input kW are different quantities. An energy assessment also needs actual load and operating hours.
What information is needed for a quotation?
Provide the industry or equipment, target temperature, approximate duty, flow, ambient conditions, operating hours and details of the existing system.
| Data Section | Description | Units | VG DS 55 | VG DS 75 | VG DS 85 | VG DS 125 | VG DS 165 | VG DS 200 |
|---|---|---|---|---|---|---|---|---|
| Technical Data | Cooling Capacity | kw | 55 | 76 | 85 | 117 | 155 | 200 |
| Cooling Capacity | kcal/h | 47.300 | 65.360 | 73.100 | 100.620 | 133.300 | 172.000 | |
| Compressor | Refrigerant Circuits | Quantity | 1 | 1 | 1 | 1 | 1 | 1 |
| Number of compressors | Quantity | 2 | 2 | 2 | 2 | 2 | 2 | |
| Evaporator | Type | – | PLATE TYPE | SHELL & TUBE | SHELL & TUBE | SHELL & TUBE | SHELL & TUBE | SHELL & TUBE |
| Water Flow | m³/h | 9,4 | 13 | 14,6 | 20,1 | 26,6 | 34,4 | |
| Electrical Specifications | Power Supply | V-phz-Hz | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 |
| Fan | Fans | Quantity | 2 | 2 | 2 | 2 | 2 | 4 |
| Hydraulic | Water Tank | LT | 250 | 300 | 300 | 350 | 350 | OPT. |
| Water Pump | HP | 3 | 4 | 3 | 5,5 | 5,5 | OPT. | |
| Water Connections | inch | 2” | 2” | 2” | 2 1/2” | 3” | 3” | |
| Dimension | Length | mm | 1750 | 2680 | 2680 | 2825 | 2825 | 3000 |
| Width | mm | 800 | 1000 | 1000 | 1250 | 1250 | 2350 | |
| Height | mm | 1600 | 1320 | 1320 | 2000 | 2000 | 2350 | |
| Weight | Transport Weight | kg | 380 | 810 | 830 | 900 | 970 | 1000 |
Confirm rating temperatures, current model availability and options when requesting a quotation.
VEGA CHİLLERS
Your reliable partner for chiller sales and maintenance